Migrating and Upgrading FS20 Sinteso Fire Panels
Upgrading Control Panels from V5.2 to V6.0
- If no changes occurred in the fire system, then no re-import of the SiB-X metafile is required in Desigo CC.
Upgrading Control Panels from V6.0 to V7.0
- Re-import of the V7.0 SiB-X metafile is required in Desigo CC.
Upgrade Desigo CC from Previous Versions
When you upgrade Desigo CC from V3.x/V4.x to V5.0, just follow the standard Desigo CC upgrade procedure.
Then, in the Desigo CC project, re-import the SiB-X metafile on each fire system to apply the latest library modifications.
Expanding Control Panels
It is possible to expand the fire panels as follows:
- FC2020 to FC2040
- FC2020 to FC2060
- FC2040 to FC2060
A new import of the SiB-X metafiles is required. Existing object references in graphics, macros, user-defined views, schedules and so on are still valid after the new SiB-X import.
Replacing NK823x as a router for the SafeDlink communication
NK823x used to be applied as a router for the fire networks in DMS8000 installations. In connection to Desigo CC, NK823x routing services can no longer support fire networks.