Configure Tile

  1. Click the Extended Operation tab.
  1. Enter the value for each required property and click Apply.
Type and source of hazard

The syntax is the same as the one used for creating libraries and graphics. The new configuration is used on tiles, reports, and the BIM Viewer.

 

Example configuration for Desigo Room Automation 1.20

Property

Value

Alternative syntax

Room object model and function

GMS_s1_room_ctl_EOT_BA_RDS1_APPL_R_10

GMS_Aggregator;Function_1

Room operating mode path

.ROpModDtr;.PrOpMod_Present_Value

 

Room temperature path

.RHvacCoo;.RTemp_Present_Value?.RHvacCoo.RTemp;.Present_Value

 

Room humidity path

.RHvacCoo;.RHuRel_Present_Value?.RHvacCoo.RHuRel;.Present_Value

 

Room air quality path

RHvacCoo;.RAQualInd_Present_Value

 

Value for Good

4

Value from the subsystem

Value for OK

3

Value from the subsystem

Value for Poor

2

Value from the subsystem

Room heating/cooling state path

.RHvacCoo.HCStaDtr;.HCSta_Present_Value

 

Value for Heat

2

Value from the subsystem

Value for Cool

3

Value from the subsystem

Room energy efficiency indication

.RGrnLf;.REei_Present_Value

 

Value for Excellent

5

Value from the subsystem

Value for Good

4

Value from the subsystem

Value for Satisfactory

3

Value from the subsystem

Value for Poor

2

Value from the subsystem

Room windows state path

.RHvacCoo;.RWndSta_Present_Value?.RHvacCoo.RWndSta;.Present_Value

 

Value for open

1

Value from the subsystem

Room presence detector path

.RHvacCoo;.RPscDet_Present_Value

 

Value for occupied

1

Value from the subsystem

Value for Unoccupied

0

Value from the subsystem

(BIM) Room air quality …

.RHvacCoo;.RAQual_Present_Value

Only required on BIM projects.

(BIM) Room light object model …

GMS_s1_room_ctl_EOT_BA_RDS1_APPL_Lgt11_10

Only required on BIM projects.

(BIM) Room light value path

;.LgtCmd_Present_Value

Only required on BIM projects.

(BIM) Room blind object model …

GMS_s1_room_ctl_EOT_BA_RDS1_APPL_Shd11_10

Only required on BIM projects.

(BIM) Room blind value path height

;.BlsCmd_Present_Value.Height

Only required on BIM projects.

(BIM) Room blind value path angle

;.BlsCmd_Present_Value.Angle

Only required on BIM projects.