Acknowledging Common Alarm

Scenario: As the service technician, you want to acknowledge all pending alarms for an automation station. Common alarms are used to avoid acknowledging multiple alarms.

  1. Desigo firmware 1.21.40.xx or higher must be installed on the automation station.
  1. Select Project > Field Networks > [Network name] > [Automation station] > Infrastructure, Automation station status monitoring.
  2. In the Extended Operation tab, select the Acknowledge property.
  3. Click Acknowledge All.
  1. All alarms for this segment are acknowledged.