Acknowledging Common Alarm
Scenario: As the service technician, you want to acknowledge all pending alarms for an automation station. Common alarms are used to avoid acknowledging multiple alarms.
- Desigo firmware 1.21.40.xx or higher must be installed on the automation station.
- Select Project > Field Networks > [Network name] > [Automation station] > Infrastructure, Automation station status monitoring.
- In the Extended Operation tab, select the Acknowledge property.
- Click Acknowledge All.
- All alarms for this segment are acknowledged.