Check the Client/FEP Project Consistency
It is recommended to check the Client/FEP project’s consistency using the following procedure before launching the Installed Client. This is used for running diagnostics on the Client/FEP project.
- You have closed SMC, if running.
- In the StartSmc.bat file under [installation drive:]\[installation folder]\GMSMainProject\bin you have added the /support switch for the project for which you want to perform the consistency check.
- In the SMC tree, select Projects > [project].
- Click Check Consistency .
- The system internally checks the validity for a project verifying the project configuration such as ports, languages, certificates against the Server.
It also checks the system configuration information and displays a message asking if you want to open the log file now.
- Click Yes to open the log and check for any errors.
- A log file opens in the default editor. The log file is also saved on the disk at the path
[installation drive:]\[installation folder]\GMSMainProject\log in the format [Project name]_[DD MM YYYY]_[HHMMSS].