GmsInt64 Configuration
GmsInt64 Type Configuration Data | ||
Data | Use | Description |
GmsType | Mandatory | GMSINT64 |
Attributes | Optional | Object containing the attributes of the property. For more details, see Table GmsInt64 Attributes, below. The empty object (“Attributes”: { }) resets the attributes data. |
GmsInt64 Attributes | ||
Data | Use | Description |
Valid | Optional | Validity flag. If false, the display data is set but considered invalid. |
Properties | Optional | Object containing the valid range values. For more details see Table GmsInt64 Properties. If the object is empty (“Properties”: { }), the range values are reset, and the range is |
UnitText | Optional | Object containing the engineering unit data. For more details in GmsInt Configuration see, Table Engineering Unit. If the object is empty (“UnitText”: { }), the engineering unit is reset. |
GmsInt64 Properties | ||
Data | Use | Description |
Min | Optional | Min value |
Max | Optional | Max value |
The values Min and Max must respect the following limits: -9223372036854775808 ÷ 9223372036854775807.
Example
{
"Name": "Long_Value",
"PvssType": {
"PvssType": "LONG",
"Status": {
"Stat": true,
"DisplOffNormal": true,
"NormalValue": -99
}
},
"VL": true,
"AL": true,
"DL0": true,
"DL1": true,
"DL2": true,
"DL3": true,
"Persist": true,
"GroupId": "CONFIG",
"Description": [ { "Culture": "en-US", "Text": "Long Value" } ],
"Display": {
"Valid": true,
"Icon": {
"Name": "Op_DP_Generic_None_001.png"
}
},
"GmsType": {
"GmsType": "GMSINT64",
"Attributes": {
"Valid": true,
"UnitText": {
"TextGroup": "MyText",
"Unit": "§"
},
"Properties":{
"Min": -40000,
"Max": 40000
}
}
}
}
The following image shows the corresponding fields in the Models & Functions tab: