Ensuring Data Consistency
Scenario: Data inconsistency occurred between the system database and the automation station since the application was newly loaded. You must perform an offline import to eliminate these inconsistencies. The automation station reports such data inconsistencies with a COV to Desigo CC. Data inconsistencies occur on the automation station if the program change time has changed (the application was re-loaded).
NOTE:
The feature is supported by Desigo automation station version 6 and higher.
- The data inconsistency is displayed on the Alarm Summary bar under Status of the alarm class.
- System Manager is in Engineering mode.
- On the Alarm Summary bar, click Status.
- A filtered alarm details list displays. The error message
Configuration outdated (Download or re-import required)
displays.
- Select the alarm line.
- Select the Automation station in the Source column to identify the impacted automation station.
- Do the following:
a. Use ABT Site to download the application program to the automation station.
b. Import the current s1x file for the impacted automation station.
- After successfully importing or download, the message
Up to date
displays under the Consistency property.
- The error message is removed from the alarm summary bar.