Assign a Function for h,x diagram

A function must be assigned to the aggregator before the h,x diagram can be displayed in the graphic.

  • The required data points are assigned to the h,x diagram in the View tab.
  • Clear the Manual Navigation check box.
  1. In the System Browser, select Logical View.
  1. Select Logical > [Hierarchy] > [Ventilation plant] > [h,x diagram].
  1. Select the Object Configurator tab.
  1. In the Settings expander, select Function, and option FnctMollierChartPX from the drop-down list.
    NOTE: Select All to see all functions.
  1. Click Save .
  1. The ,odify function must be adapted for the extract air sensor is used for the h,x diagram instead of the room sensor.
  • The h,x diagram is configured (is item 6 is not required) and can be tested.